Industrial Grade Dupont™ SFP-2880 Ultrafiltration Module – 77 m² For Water Purification
Product Details:
| Place of Origin: | China |
| Brand Name: | Dupont |
| Certification: | CE |
| Model Number: | SFP-2880 |
| Document: | UF-IntegraTec-P-Series-PVDF...en.pdf |
Payment & Shipping Terms:
| Minimum Order Quantity: | 1 pc |
|---|---|
| Price: | Negotiable |
| Packaging Details: | standard export packing |
| Delivery Time: | 5- 8 work days |
| Payment Terms: | ,T/T |
| Supply Ability: | 60000 Units per Month |
|
Detail Information |
|||
| Flux Range Of This Component: | 40–90 LMH (24–53 Gfd) At 25°C | Flow Rate Of This Component: | 2.0–6.9 M³/hr (8.8–30.4 Gpm) |
|---|---|---|---|
| Temperature Limits Of This Component: | 1–40°C (34–104°F) | Max Operating TMP Of This Component: | 2.1 Bar (30.5 Psi) |
| Chemical Tolerance Of This Component: | Withstands Up To 2,000 Mg/L NaOCl | Optimized Design Of This Component: | 77m2 |
| Wide Application Range Of This Component: | Suitable For Treating Surface Water, Seawater, Municipal Drinking Water Production | Membrane Type: | Industrial Grade Ultrafiltration Membrane Components |
Product Description
Industrial Grade Dupont™ SFP-2880 Ultrafiltration Module – 77 m² For Water Purification
Product Overview
Key Features
- Advanced Filtration Performance: Removes bacteria, viruses, and colloids with high efficiency; achieves filtrate turbidity below 0.1 NTU and SDI under 2.5; ideal protection for reverse osmosis systems
- Engineered Durability: Chemical-resistant PVDF membrane withstands extreme pH conditions; U-PVC housing eliminates need for pressure vessels; operating temperature range supports global deployments
- High-Efficiency Design: Industry-leading membrane area enables high flow rates; outside-in flow handles high solids loading; reduced backwash frequency lowers water consumption
- Operational Reliability: Consistent performance in municipal and industrial settings; minimal maintenance requirements; compatible with automated control systems
Technical Specifications
| Attribute | Value |
|---|---|
| UF Module Flux Range | 40–90 LMH (24–53 gfd) at 25°C |
| Flow Rate per Module | 2.0–6.9 m³/hr (8.8–30.4 gpm) |
| UF Module Temperature Limits | 1–40°C (34–104°F) |
| UF Module Max Operating TMP | 2.1 bar (30.5 psi) |
| Chemical Tolerance | Withstands up to 2,000 mg/L NaOCl |
| Membrane Area | 77m² |
| Membrane Type | Industrial Grade Ultrafiltration Membrane Components |
Product Specifications
| Model | Type | Part # | Membrane Area (m²/ft²) | Volume (Liters/Gallons) | Weight (Kg/lbs) |
|---|---|---|---|---|---|
| SFP-2880 | Pretreatment | 280934 | 77 / 829 | 39 / 10.3 | 61 / 135 (empty), 100 / 220 (water filled) |
| SFD-2880 | NSF/ANSI 61 Drinking water | 324169 | 77 / 829 | 39 / 10.3 | 61 / 135 (empty), 100 / 220 (water filled) |
Operating Parameters
| Parameter | SI Units | US Units |
|---|---|---|
| Filtrate Flux @ 25ºC | 40-120 l/m²/hr | 24-70 gfd |
| Flow range | 3.1-9.3 m³/hr | 13.6 - 40.9 gpm |
| Temperature | 1-40ºC | 34-104ºF |
| Max. inlet module pressure (@ 20ºC) | 6.25 bar | 93.75 psi |
| Max. operating TMP | 2.1 bar | 30 psi |
| Max operating air scour flow | 12 nm³/hr | 7.1 scfm |
| Max backwash pressure | 2.5 bar | 36 psi |
| Operating pH | 2-11 | |
Important: If operating limits and guidelines given in this bulletin are not strictly followed, the limited warranty will be null and void. To prevent biological growth during system shutdowns, it is recommended that preservative solution be injected into the membrane modules.
Module Installation
Want to Know more details about this product